1 change: 1 addition & 0 deletions rct229/rulesets/ashrae9012022/__init__.py
Original file line number Diff line number Diff line change
Expand Up @@ -74,6 +74,7 @@
"prm9012022rule23z21": "section12rule5",
"prm9012022rule93e12": "section21rule19",
"prm9012022rule93e20": "section22rule43",
"prm9012022Rule43f22": "section22rule44",
}

section_list = [
Expand Down
Original file line number Diff line number Diff line change
Expand Up @@ -246,11 +246,20 @@ def does_chiller_performance_match_curve(chiller: dict, curve_set: str) -> bool:
for expected_plr in EXPECTED_VALIDATION_PLR
]
):
eir_plr = (
plr_coefficients[0]
+ plr_coefficients[1] * plr
+ plr_coefficients[2] * plr**2
)
if len(plr_coefficients) == 3:
eir_plr = (
plr_coefficients[0]
+ plr_coefficients[1] * plr
+ plr_coefficients[2] * plr**2
)
elif len(plr_coefficients) == 4:
eir_plr = (
plr_coefficients[0]
+ plr_coefficients[1] * plr
+ plr_coefficients[2] * plr**2
+ plr_coefficients[3] * plr**3
)

eir_ft = (
eir_f_t_coefficients[0]
+ eir_f_t_coefficients[1] * chwt
Expand Down
3 changes: 3 additions & 0 deletions rct229/rulesets/ashrae9012022/section22/__init__.py
Original file line number Diff line number Diff line change
Expand Up @@ -4,8 +4,11 @@
__all__ = [
"section22rule42",
"section22rule43",
"section22rule44",
]

SHORT_NAME = "HVAC-CHW"


def __getattr__(name):
if name in __all__:
Expand Down
163 changes: 163 additions & 0 deletions rct229/rulesets/ashrae9012022/section22/section22rule44.py
Original file line number Diff line number Diff line change
@@ -0,0 +1,163 @@
from rct229.rule_engine.rule_base import RuleDefinitionBase
from rct229.rule_engine.rule_list_indexed_base import RuleDefinitionListIndexedBase
from rct229.rule_engine.ruleset_model_factory import produce_ruleset_model_description
from rct229.rulesets.ashrae9012022 import PROPOSED
from rct229.rulesets.ashrae9012022.ruleset_functions.does_chiller_performance_match_curve import (
J4_CURVE,
does_chiller_performance_match_curve,
)
from rct229.schema.config import ureg
from rct229.schema.schema_enums import SchemaEnums
from rct229.utils.assertions import getattr_
from rct229.utils.jsonpath_utils import find_all
from rct229.utils.pint_utils import CalcQ
from rct229.utils.std_comparisons import std_equal

CHILLER_COMPRESSOR = SchemaEnums.schema_enums["ChillerCompressorOptions"]
UNDETERMINED_MSG = "FAIL unless manufacturer full- and part-load data is provided to support the modeled curves."


class PRM9012022Rule43f22(RuleDefinitionListIndexedBase):
"""Rule 44 of ASHRAE 90.1-2022 Appendix G Section 22 (Chilled Water Loop)"""

def __init__(self):
super(PRM9012022Rule43f22, self).__init__(
rmds_used=produce_ruleset_model_description(
USER=False, BASELINE_0=False, PROPOSED=True
),
each_rule=PRM9012022Rule43f22.ChillerRule(),
index_rmd=PROPOSED,
id="22-44",
description="here part-load performance of chillers in the proposed design is not available, and the design temperature across the condenser is 10°F, "
"the performance curves in Normative Appendix J, as referenced in Table J-1, shall be modeled for the specified chiller.",
ruleset_section_title="HVAC - Chiller",
standard_section=" Table G3.1 #10b Proposed Column",
is_primary_rule=True,
list_path="$.chillers[*]",
rmd_context="ruleset_model_descriptions/0",
)

def create_data(self, context, data):
rmd_p = context.PROPOSED

return {
"non_process_chw_coil_loop_dict_p": {
chw_loop["id"]: [
chw_child_loop_id
for chw_child_loop_id in find_all(
f'$.child_loops[*][?(@.type="COOLING")].id', chw_loop
)
]
for chw_loop in find_all(
f'$.fluid_loops[*][?(@.type="COOLING")]', rmd_p
)
}
}

class ChillerRule(RuleDefinitionBase):
def __init__(self):
super(PRM9012022Rule43f22.ChillerRule, self).__init__(
rmds_used=produce_ruleset_model_description(
USER=False, BASELINE_0=False, PROPOSED=True
),
required_fields={
"$": ["cooling_loop"],
},
manual_check_required_msg=UNDETERMINED_MSG,
)

def is_applicable(self, context, data=None):
chiller_p = context.PROPOSED
cooling_loop_p = chiller_p["cooling_loop"]
non_process_chw_coil_loop_dict_p = data["non_process_chw_coil_loop_dict_p"]

return (
# Check if chiller primary loop serves hvac systems
cooling_loop_p in non_process_chw_coil_loop_dict_p
# Check if chiller serves a loop that has child loops and those child loops serve hvac systems
or cooling_loop_p in non_process_chw_coil_loop_dict_p[cooling_loop_p]
)

def get_calc_vals(self, context, data=None):
chiller_p = context.PROPOSED

rated_capacity_p = getattr_(chiller_p, "chillers", "rated_capacity")
compressor_type_p = getattr_(chiller_p, "chillers", "compressor_type")

if chiller_p.get("condensing_loop") is None:
if rated_capacity_p < 150 * ureg("ton"):
curve_set_list_p = [J4_CURVE.A, J4_CURVE.K]
else:
curve_set_list_p = [J4_CURVE.B, J4_CURVE.L]

else:
if compressor_type_p in (
CHILLER_COMPRESSOR.POSITIVE_DISPLACEMENT,
CHILLER_COMPRESSOR.SCROLL,
CHILLER_COMPRESSOR.SCREW,
):
if rated_capacity_p < 75 * ureg("ton"):
curve_set_list_p = [J4_CURVE.C, J4_CURVE.M]
elif rated_capacity_p < 150 * ureg("ton"):
curve_set_list_p = [J4_CURVE.D, J4_CURVE.N]
elif rated_capacity_p < 300 * ureg("ton"):
curve_set_list_p = [J4_CURVE.E, J4_CURVE.O]
elif rated_capacity_p < 600 * ureg("ton"):
curve_set_list_p = [J4_CURVE.F, J4_CURVE.P]
else:
curve_set_list_p = [J4_CURVE.G, J4_CURVE.Q]

if compressor_type_p == CHILLER_COMPRESSOR.CENTRIFUGAL:
if rated_capacity_p < 150 * ureg("ton"):
curve_set_list_p = [J4_CURVE.H, J4_CURVE.R]
elif rated_capacity_p < 300 * ureg("ton"):
curve_set_list_p = [J4_CURVE.H, J4_CURVE.S]
elif rated_capacity_p < 400 * ureg("ton"):
curve_set_list_p = [J4_CURVE.I, J4_CURVE.T]
else:
curve_set_list_p = [J4_CURVE.J, J4_CURVE.U]

design_leaving_condenser_temperature_p = getattr_(
chiller_p, "chillers", "design_leaving_condenser_temperature"
)
design_entering_condenser_temperature_p = getattr_(
chiller_p, "chillers", "design_entering_condenser_temperature"
)

return {
"curve_set_list_p": curve_set_list_p,
"design_leaving_condenser_temperature_p": CalcQ(
"temperature", design_leaving_condenser_temperature_p
),
"design_entering_condenser_temperature_p": CalcQ(
"temperature", design_entering_condenser_temperature_p
),
}

def manual_check_required(self, context, calc_vals=None, data=None):
chiller_p = context.PROPOSED
curve_set_list_p = calc_vals["curve_set_list_p"]

return not any(
does_chiller_performance_match_curve(chiller_p, curve_set)
for curve_set in curve_set_list_p
)

def rule_check(self, context, calc_vals=None, data=None):
chiller_p = context.PROPOSED
curve_set_list_p = calc_vals["curve_set_list_p"]
design_leaving_condenser_temperature_p = calc_vals[
"design_leaving_condenser_temperature_p"
]
design_entering_condenser_temperature_p = calc_vals[
"design_entering_condenser_temperature_p"
]

return any(
does_chiller_performance_match_curve(chiller_p, curve_set)
Copy link
Collaborator

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

The function name is is_chiller_performance_app_j or does_chiller_performance_match_curve?
I saw this function is ready merged: is_chiller_performance_app_j
Should you change to is_chiller_performance_app_j function?
Also, the PR contains does_chiller_performance_match_curve, should we remove this?

Copy link
Collaborator Author

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

As discussed during the standup, the is_chiller_performance_app_j function name was changed to does_chiller_performance_match_curve.

for curve_set in curve_set_list_p
) and std_equal(
design_entering_condenser_temperature_p
- design_leaving_condenser_temperature_p,
10 * ureg("delta_degF"),
)
Loading