Zigzag winding transformer modelling comment #1177
New issue
Have a question about this project? Sign up for a free GitHub account to open an issue and contact its maintainers and the community.
By clicking “Sign up for GitHub”, you agree to our terms of service and privacy statement. We’ll occasionally send you account related emails.
Already on GitHub? Sign in to your account
base: main
Are you sure you want to change the base?
Conversation
Signed-off-by: Nitish Bharambe <[email protected]>
Signed-off-by: Nitish Bharambe <[email protected]>
Signed-off-by: Nitish Bharambe <[email protected]>
| 
           @nitbharambe See below. The zero-sequence impedance of zigzag transformer, is approximately  https://www.linkedin.com/pulse/advantages-yzn-transformers-over-dyn-small-250kva-ebrahim-barghamadi/  | 
    
Signed-off-by: Nitish Bharambe <[email protected]>
| 
           Clear enough. Thanks for sharing the article. Quite informative!  | 
    
          
 | 
    
| 
           @nitbharambe why adding one comment causes CI to fail?  | 
    
          
 unrelated to this PR. Nightly is also failing. I'm on it.  | 
    
| 
           @TonyXiang8787 Different issue. Nightly is failing too.  | 
    



I am not sure about the exact modelling. 0.1 definitely seems incorrect. Is Maybe it is such that the impedance becomes twice as rating is of a single z winding? I see this change in d3fcf1d. @TonyXiang8787 need your input.